El BWR2 transformer winding temperature indicator is designed for oil-immersed transformer winding temperature indication, transformer cooling control, alarm output and over-temperature protection. It is also known as a WTI gauge for transformer, winding temperature indicator o transformer winding temperature controller.The product uses a compound transmitter and a pointer-type temperature indicator to display simulated transformer winding temperature. It is suitable for transformer control cabinets, transformer temperature monitoring panels and field-mounted temperature indication on oil-immersed power transformers.

BWR2 WTI Gauge for Oil-Immersed Transformer Temperature Monitoring

The BWR2 WTI gauge is used where oil-immersed transformers require local winding temperature indication, cooling control, signal alarm and trip protection. It helps operators monitor transformer thermal condition and supports safer operation under changing load conditions.

For transformer projects requiring remote display or signal transmission, the BWR2 winding temperature indicator can be configured with optional output and digital temperature display according to the selected model.

How the BWR2 Transformer Winding Temperature Indicator Works

The BWR2 transformer winding temperature indicator works by thermal simulation. The temperature bulb is installed in the compound transmitter, and the compound transmitter is inserted into the thermometer pocket on the top oil area of the transformer tank.

When the transformer operates without load, the indicated value reflects transformer oil temperature. When the transformer is loaded, the current signal from the transformer current transformer is adjusted by the compound transmitter and converted into additional heating on the sensing element. The final indicated value represents the combined effect of transformer top oil temperature and load-related winding temperature rise.

This working principle makes the product suitable for traditional transformer winding temperature indication, transformer cooling control, alarm contact output and over-temperature protection.

Key Functions of BWR2 Transformer Winding Temperature Controller

  • Winding temperature indication for oil-immersed transformers
  • Transformer top oil temperature and load-current thermal simulation
  • Adjustable switch contacts for alarm, cooling control and trip protection
  • Optional signal output for remote temperature indication
  • Optional digital temperature display for remote display and signal control
  • Suitable for transformer control cabinets and transformer temperature monitoring panels
  • Designed for transformer cooling system control and over-temperature protection

BWR2 Winding Temperature Indicator Model Selection Guide

The BWR2 transformer winding temperature indicator can be selected according to switch quantity, output signal and special environmental application requirements. The model code helps define the configuration for transformer temperature indication, signal output and field environment.

BWR2 Naming rules for product models

Elemento del Código Modelo Código Significado
Series de productos BWR2 Transformer winding temperature controller / winding temperature indicator series
Cantidad de interruptores de control Configurado según las necesidades Cantidad de contactos del interruptor seleccionada de acuerdo con los requisitos del proyecto
Código de función A Salida Pt100
Código de función J Salida de 4-20 mA, tipo de dos hilos
Código Especial de Medio Ambiente TH Adecuado para zonas tropicales húmedas
Código Especial de Medio Ambiente TA Adecuado para zonas tropicales secas
Código Especial de Medio Ambiente T Adecuado para zonas tropicales secas y húmedas

BWR2 Transformer WTI Gauge Technical Specifications

Nombre del producto Indicador de temperatura de los devanados del transformador
Series de productos BWR2 Series
Solicitud Indicación y control de la temperatura de los devanados de transformadores sumergidos en aceite
Temperatura ambiente de funcionamiento -40°C to +65°C
Humedad relativa ≤95% a 25 °C
Rango de medición 0°C to 160°C
Precisión Clase 1.5; error máximo permitido en el punto de detección: ±2,4 °C
Contactos del interruptor 4 adjustable switch contacts
Potencia nominal del interruptor CA 220 V / 5 A
Longitud capilar Según el último grupo de dígitos del número de instrumento
Grado de protección IP55

BWR2 Compound Transmitter for Transformer Winding Temperature Control

The compound transmitter is an important part of the BWR2 transformer winding temperature indicator. It receives the current signal from the transformer current transformer and works with the temperature sensing element to simulate winding temperature rise under load.

This configuration allows the winding temperature indicator to provide local temperature indication and control signals for transformer cooling, alarm and protection circuits.

BWR2 Installation diagram of composite transmitter

No. Nombre del componente
1 Current Transformer
2 Transmitter
3 Heating Element
4 Temperature Sensing Element
5 Tubo capilar
Componente Compound Transmitter
Temperatura ambiente de funcionamiento -40°C to +65°C
Humedad relativa ≤95% a 25 °C
Señal de entrada Transformer CT secondary current, 0.5A to 5.0A
Señal de salida Pt100 platinum resistance signal
Tamaño del bulbo de temperatura Φ18 × 150 mm
Rosca de montaje M27 × 2 mm
Grado de protección IP55

BWR2 Winding Temperature Indicator Dimensions and Structure

The BWR2 winding temperature indicator and compound transmitter are supplied with mechanical dimension drawings for transformer side-wall installation, thermometer pocket installation and capillary tube routing. Please confirm the final product drawing before transformer body design, panel design or site installation.

BWR2 Dimensional drawing of winding thermometer and composite transmitter

BWR2 Introduction diagram of component names for winding thermometer

No. Nombre del componente No. Nombre del componente
1 Puntero de ajuste del contacto del interruptor 7 Cable Entry Hole
2 Puntero indicador de temperatura 8 Compound Transmitter
3 Puntero de registro de la temperatura máxima 9 Perno de sellado
4 Perilla de reinicio del indicador de grabación máxima 10 Tornillo de montaje
5 Perilla de ajuste a cero 11 Bulbo de temperatura / Sensor de temperatura
6 Orificio de entrada de cable para conector de manguera recubierta de plástico de Φ16 12 Tubo capilar recubierto con una manguera de acero inoxidable

Adjustable Switch Contacts for Transformer Alarm and Cooling Control

The BWR2 winding temperature indicator includes adjustable switch contacts that can be used for transformer signal alarm, cooling control and over-temperature trip protection. The contact settings can be configured according to transformer operation and protection requirements.

Contacto de interruptor Configuración predeterminada de fábrica Uso típico
K1 50°C Configurado de acuerdo con los requisitos del proyecto
K2 75°C Configurado de acuerdo con los requisitos del proyecto
K3 100 °C Configurado de acuerdo con los requisitos del proyecto
K4 120°C Configurado de acuerdo con los requisitos del proyecto

BWR2 WTI Gauge Wiring Diagram Overview

The BWR2 transformer winding temperature controller supports wiring for control switch output, CT current input and Pt100 signal output according to the selected model and actual product wiring diagram.

Elemento de cableado Función
K1 / K2 / K3 / K4 Terminales de salida del interruptor de control
CT Input Transformer current transformer secondary current input
Salida Pt100 Salida de señal de temperatura por resistencia de platino

Optional Digital Temperature Display for BWR2 WTI Gauge

The optional digital temperature display can be used together with the BWR2 transformer winding temperature indicator for remote temperature indication, signal transmission and signal control. It is suitable for transformer control panels, remote monitoring cabinets and centralized temperature display applications.

Accesorio Pantalla digital de temperatura
Temperatura ambiente de funcionamiento De -10 °C a +50 °C
Humedad relativa ≤85%
Fuente de alimentación CA/CC 100–265 V, 50–60 Hz
Señal de salida Corriente analógica de 4 a 20 mA, comunicación RS485
Tipo de pantalla Pantalla digital de tubo
Precisión Clase 1.0

Digital Temperature Display Model Selection for BWR2 WTI Gauge

La pantalla digital de temperatura opcional puede seleccionarse según la señal de entrada, la fuente de alimentación de trabajo, la cantidad de relés y la función opcional de salida o comunicación. Se utiliza para la indicación remota de temperatura, la transmisión de señales y la salida de control en paneles de monitoreo de transformadores.

Selección del instrumento digital de visualización de temperatura BWX

Elemento de selección Código Significado
Tipo de producto BWX Pantalla digital de temperatura
Señal de entrada A Entrada Pt100
Señal de entrada B Entrada de 4-20 mA, tipo de dos hilos
Fuente de alimentación en funcionamiento 2 CA 220 V
Fuente de alimentación en funcionamiento 5 CA/CC 100–264 V
Cantidad de relés 0 / 1 / 2 0: ninguno; 1: un relé; 2: dos relés
Función opcional E Salida de 4-20 mA
Función opcional F Función de comunicación RS485

Dimensiones de instalación del display digital de temperatura

The optional digital temperature display is designed for embedded panel installation. It can be mounted into the reserved opening of the control panel for remote winding temperature indication and signal control.

Diagrama de dimensiones de instalación del instrumento digital de visualización de temperatura BWX

Método de instalación Instalación empotrada
Tamaño de la abertura del panel 153 × 77 mm
Dimensiones totales 160 × 80 × 120 mm

Installation Overview for BWR2 Transformer Winding Temperature Indicator

The BWR2 transformer winding temperature indicator should be installed vertically on the transformer body. The temperature bulb should be inserted into the thermometer pocket filled with transformer oil, and the capillary tube should be properly fixed during installation.

...

Elemento de instalación Requisito
Instalación del indicador Se fija verticalmente a la pared lateral del transformador con 3 tornillos M6
Instalación del bulbo de temperatura El compartimento del termómetro debe llenarse con aceite para transformadores antes de la instalación
Posición del bulbo de temperatura El bulbo de temperatura debe insertarse hasta el fondo del compartimento del termómetro y fijarse
Fijación de tubos capilares El tubo capilar debe fijarse correctamente cada 300 mm
Tubo capilar adicional El tubo capilar sobrante debe enrollarse con un diámetro superior a 200 mm y fijarse adecuadamente
Sección de cables de conexión Se recomienda una sección transversal del cable de 2,5 mm²

Applications of BWR2 Transformer Winding Temperature Indicator

The BWR2 transformer winding temperature indicator is suitable for oil-immersed transformer temperature indication, transformer cooling control and over-temperature protection applications. It can be used in transformer substations, industrial power distribution systems, power plants and transformer control cabinets.

  • Transformadores de potencia sumergidos en aceite
  • Transformer cooling control systems
  • Transformer temperature alarm and trip circuits
  • Paneles de monitoreo de transformadores de subestaciones
  • Gabinetes de control para transformadores
  • Aplicaciones de indicación remota de temperatura y transmisión de señales

WTI Gauge vs Fiber Optic Winding Temperature Monitoring

A traditional WTI gauge indicates simulated winding temperature based on transformer oil temperature and load-current thermal simulation. It is suitable for transformer winding temperature indication, cooling control and alarm protection.

Fiber optic winding temperature monitoring is different. It uses fiber optic temperature sensors installed near the winding area for direct hot spot temperature measurement. For transformer projects that require direct winding hot spot measurement, fiber optic temperature monitoring can be considered together with traditional WTI temperature indication.

Artículo Medidor BWR2 WTI Fiber Optic Winding Temperature Monitoring
Método de medición de la temperatura Thermal simulation Direct optical temperature measurement
Uso típico Local indication, alarm, cooling control and trip protection Direct winding hot spot monitoring
Posición de instalación Bolsillo y pared lateral del termómetro del transformador Near winding hot spot measurement points

Frequently Asked Questions About BWR2 Transformer Winding Temperature Indicator

What is a BWR2 transformer winding temperature indicator?

The BWR2 transformer winding temperature indicator is a WTI gauge used for oil-immersed transformer winding temperature indication, cooling control, alarm output and over-temperature protection.

What does WTI mean in transformer temperature monitoring?

WTI means winding temperature indicator. In transformer applications, it is commonly used to indicate simulated transformer winding temperature and provide control signals for transformer cooling and protection systems.

How does the BWR2 WTI gauge indicate winding temperature?

The BWR2 WTI gauge uses top oil temperature and load-current thermal simulation. The compound transmitter adds load-related temperature rise to the sensing element, allowing the indicator to show simulated transformer winding temperature.

Can the BWR2 winding temperature indicator support remote display?

Yes. The BWR2 transformer winding temperature indicator can be used with an optional digital temperature display for remote indication, signal transmission and control output according to the selected configuration.

What is the difference between a WTI gauge and fiber optic hot spot monitoring?

A WTI gauge uses thermal simulation, while fiber optic hot spot monitoring directly measures temperature at selected winding measurement points. The two methods can serve different transformer monitoring requirements.

¿Dónde está instalado el bulbo de temperatura?

The temperature bulb is installed in the compound transmitter, and the compound transmitter is inserted into the thermometer pocket on the top oil area of the transformer tank.

Request BWR2 Transformer Winding Temperature Indicator Configuration

For project selection, please provide the transformer type, required output signal, switch contact requirement, remote display requirement and installation environment. INNOFZ can help select a suitable BWR2 winding temperature indicator configuration for your transformer temperature monitoring application.