Этот BWR2 transformer winding temperature indicator is designed for oil-immersed transformer winding temperature indication, transformer cooling control, alarm output and over-temperature protection. It is also known as a WTI gauge for transformer, winding temperature indicator или transformer winding temperature controller.The product uses a compound transmitter and a pointer-type temperature indicator to display simulated transformer winding temperature. It is suitable for transformer control cabinets, transformer temperature monitoring panels and field-mounted temperature indication on oil-immersed power transformers.

BWR2 WTI Gauge for Oil-Immersed Transformer Temperature Monitoring

The BWR2 WTI gauge is used where oil-immersed transformers require local winding temperature indication, cooling control, signal alarm and trip protection. It helps operators monitor transformer thermal condition and supports safer operation under changing load conditions.

For transformer projects requiring remote display or signal transmission, the BWR2 winding temperature indicator can be configured with optional output and digital temperature display according to the selected model.

How the BWR2 Transformer Winding Temperature Indicator Works

The BWR2 transformer winding temperature indicator works by thermal simulation. The temperature bulb is installed in the compound transmitter, and the compound transmitter is inserted into the thermometer pocket on the top oil area of the transformer tank.

When the transformer operates without load, the indicated value reflects transformer oil temperature. When the transformer is loaded, the current signal from the transformer current transformer is adjusted by the compound transmitter and converted into additional heating on the sensing element. The final indicated value represents the combined effect of transformer top oil temperature and load-related winding temperature rise.

This working principle makes the product suitable for traditional transformer winding temperature indication, transformer cooling control, alarm contact output and over-temperature protection.

Key Functions of BWR2 Transformer Winding Temperature Controller

  • Winding temperature indication for oil-immersed transformers
  • Transformer top oil temperature and load-current thermal simulation
  • Adjustable switch contacts for alarm, cooling control and trip protection
  • Optional signal output for remote temperature indication
  • Optional digital temperature display for remote display and signal control
  • Suitable for transformer control cabinets and transformer temperature monitoring panels
  • Designed for transformer cooling system control and over-temperature protection

BWR2 Winding Temperature Indicator Model Selection Guide

The BWR2 transformer winding temperature indicator can be selected according to switch quantity, output signal and special environmental application requirements. The model code helps define the configuration for transformer temperature indication, signal output and field environment.

BWR2 Naming rules for product models

Пункт типового кодекса Код Значение
Серия продуктов BWR2 Transformer winding temperature controller / winding temperature indicator series
Количество управляющих выключателей Настраивается в соответствии с требованиями Количество контактов выключателя выбирается в соответствии с требованиями проекта
Код функции A Выход Pt100
Код функции J Выход 4–20 мА, двухпроводной тип
Специальный кодекс об охране окружающей среды TH Подходит для влажных тропических регионов
Специальный кодекс об охране окружающей среды ТА Подходит для сухих тропических регионов
Специальный кодекс об охране окружающей среды T Подходит для сухих и влажных тропических регионов

BWR2 Transformer WTI Gauge Technical Specifications

Название продукта Индикатор температуры обмотки трансформатора
Серия продуктов BWR2 Series
Заявка Контроль и индикация температуры обмоток масляных трансформаторов
Рабочая температура окружающей среды -40°C to +65°C
Относительная влажность ≤95% при 25 °C
Диапазон измерения 0°C to 160°C
Точность Класс 1,5; максимально допустимая погрешность в точке измерения ±2,4 °C
Контакты переключателя 4 adjustable switch contacts
Номинальная мощность выключателя 220 В переменного тока / 5 А
Длина капилляра В зависимости от последней группы цифр в номере прибора
Степень защиты IP55

BWR2 Compound Transmitter for Transformer Winding Temperature Control

The compound transmitter is an important part of the BWR2 transformer winding temperature indicator. It receives the current signal from the transformer current transformer and works with the temperature sensing element to simulate winding temperature rise under load.

This configuration allows the winding temperature indicator to provide local temperature indication and control signals for transformer cooling, alarm and protection circuits.

BWR2 Installation diagram of composite transmitter

Нет. Название компонента
1 Current Transformer
2 Transmitter
3 Heating Element
4 Temperature Sensing Element
5 Капиллярная трубка
Компонент Compound Transmitter
Рабочая температура окружающей среды -40°C to +65°C
Относительная влажность ≤95% при 25 °C
Входной сигнал Transformer CT secondary current, 0.5A to 5.0A
Выходной сигнал Pt100 platinum resistance signal
Размер температурного датчика Φ18 × 150 mm
Монтажная резьба M27 × 2 мм
Степень защиты IP55

BWR2 Winding Temperature Indicator Dimensions and Structure

The BWR2 winding temperature indicator and compound transmitter are supplied with mechanical dimension drawings for transformer side-wall installation, thermometer pocket installation and capillary tube routing. Please confirm the final product drawing before transformer body design, panel design or site installation.

BWR2 Dimensional drawing of winding thermometer and composite transmitter

BWR2 Introduction diagram of component names for winding thermometer

Нет. Название компонента Нет. Название компонента
1 Указатель настройки контактов переключателя 7 Cable Entry Hole
2 Стрелка, указывающая температуру 8 Compound Transmitter
3 Указатель максимальной зарегистрированной температуры 9 Уплотнительный болт
4 Регулятор сброса указателя максимального значения записи 10 Крепежный винт
5 Ручка настройки нуля 11 Термощуп / Датчик температуры
6 Отверстие для прокладки кабеля для соединителя с пластиковым покрытием для шланга диаметром 16 12 Капиллярная трубка, обтянутая шлангом из нержавеющей стали

Adjustable Switch Contacts for Transformer Alarm and Cooling Control

The BWR2 winding temperature indicator includes adjustable switch contacts that can be used for transformer signal alarm, cooling control and over-temperature trip protection. The contact settings can be configured according to transformer operation and protection requirements.

Контакт переключателя Заводские настройки Типичные области применения
K1 50°C Настроено в соответствии с требованиями проекта
K2 75°C Настроено в соответствии с требованиями проекта
K3 100 °C Настроено в соответствии с требованиями проекта
K4 120°C Настроено в соответствии с требованиями проекта

BWR2 WTI Gauge Wiring Diagram Overview

The BWR2 transformer winding temperature controller supports wiring for control switch output, CT current input and Pt100 signal output according to the selected model and actual product wiring diagram.

Элемент электромонтажа Функция
K1 / K2 / K3 / K4 Выводные клеммы управляющего выключателя
CT Input Transformer current transformer secondary current input
Выход Pt100 Платиновый резистивный выход температурного сигнала

Optional Digital Temperature Display for BWR2 WTI Gauge

The optional digital temperature display can be used together with the BWR2 transformer winding temperature indicator for remote temperature indication, signal transmission and signal control. It is suitable for transformer control panels, remote monitoring cabinets and centralized temperature display applications.

Аксессуар Цифровой индикатор температуры
Рабочая температура окружающей среды от -10 °C до +50 °C
Относительная влажность ≤85%
Источник питания Переменный ток/переменное напряжение 100–265 В, 50–60 Гц
Выходной сигнал Аналоговый ток 4–20 мА, интерфейс RS485
Тип дисплея Цифровой трубчатый дисплей
Точность Класс 1.0

Digital Temperature Display Model Selection for BWR2 WTI Gauge

Дополнительный цифровой дисплей температуры можно выбрать в зависимости от входного сигнала, рабочего источника питания, количества реле, а также дополнительных функций вывода или связи. Он используется для дистанционного отображения температуры, передачи сигналов и управления выходами в панелях контроля трансформаторов.

Выбор цифрового прибора отображения температуры BWX

Элемент выбора Код Значение
Тип продукта BWX Цифровой индикатор температуры
Входной сигнал A Вход Pt100
Входной сигнал B Вход 4–20 мА, двухпроводной тип
Рабочий источник питания 2 220 В переменного тока
Рабочий источник питания 5 Переменный ток/переменное напряжение 100–264 В
Количество реле 0 / 1 / 2 0: нет; 1: одно реле; 2: два реле
Дополнительная функция E Выход 4–20 мА
Дополнительная функция F Функция связи RS485

Установочные размеры цифрового дисплея температуры

The optional digital temperature display is designed for embedded panel installation. It can be mounted into the reserved opening of the control panel for remote winding temperature indication and signal control.

Схема монтажных размеров цифрового индикатора температуры BWX

Способ установки Встраиваемая установка
Размер отверстия в панели 153 × 77 мм
Габаритные размеры 160 × 80 × 120 мм

Installation Overview for BWR2 Transformer Winding Temperature Indicator

The BWR2 transformer winding temperature indicator should be installed vertically on the transformer body. The temperature bulb should be inserted into the thermometer pocket filled with transformer oil, and the capillary tube should be properly fixed during installation.

...

Элемент установки Требование
Установка датчика Вертикально закреплен на боковой стенке трансформатора с помощью 3 болтов M6
Установка температурного датчика Перед установкой кармашек для термометра следует заполнить трансформаторным маслом
Положение температурного датчика Термометрический бульб следует вставить до самого дна кармашка термометра и закрепить
Крепление капиллярных трубок Капиллярную трубку следует надлежащим образом закреплять через каждые 300 мм
Дополнительная капиллярная трубка Излишки капиллярной трубки следует скрутить в спираль диаметром более 200 мм и надёжно закрепить
Раздел «Проводка» Рекомендуемое сечение одножильного провода — 2,5 мм²

Applications of BWR2 Transformer Winding Temperature Indicator

The BWR2 transformer winding temperature indicator is suitable for oil-immersed transformer temperature indication, transformer cooling control and over-temperature protection applications. It can be used in transformer substations, industrial power distribution systems, power plants and transformer control cabinets.

  • Силовые трансформаторы в масляной ванне
  • Transformer cooling control systems
  • Transformer temperature alarm and trip circuits
  • Панели контроля трансформаторов подстанций
  • Щиты управления трансформаторами
  • Применение систем дистанционного отображения температуры и передачи сигналов

WTI Gauge vs Fiber Optic Winding Temperature Monitoring

A traditional WTI gauge indicates simulated winding temperature based on transformer oil temperature and load-current thermal simulation. It is suitable for transformer winding temperature indication, cooling control and alarm protection.

Fiber optic winding temperature monitoring is different. It uses fiber optic temperature sensors installed near the winding area for direct hot spot temperature measurement. For transformer projects that require direct winding hot spot measurement, fiber optic temperature monitoring can be considered together with traditional WTI temperature indication.

Пункт Датчик BWR2 для WTI Fiber Optic Winding Temperature Monitoring
Метод измерения температуры Thermal simulation Direct optical temperature measurement
Типичные области применения Local indication, alarm, cooling control and trip protection Direct winding hot spot monitoring
Положение при установке Карман и боковая стенка термометра «Трансформер» Near winding hot spot measurement points

Frequently Asked Questions About BWR2 Transformer Winding Temperature Indicator

What is a BWR2 transformer winding temperature indicator?

The BWR2 transformer winding temperature indicator is a WTI gauge used for oil-immersed transformer winding temperature indication, cooling control, alarm output and over-temperature protection.

What does WTI mean in transformer temperature monitoring?

WTI means winding temperature indicator. In transformer applications, it is commonly used to indicate simulated transformer winding temperature and provide control signals for transformer cooling and protection systems.

How does the BWR2 WTI gauge indicate winding temperature?

The BWR2 WTI gauge uses top oil temperature and load-current thermal simulation. The compound transmitter adds load-related temperature rise to the sensing element, allowing the indicator to show simulated transformer winding temperature.

Can the BWR2 winding temperature indicator support remote display?

Yes. The BWR2 transformer winding temperature indicator can be used with an optional digital temperature display for remote indication, signal transmission and control output according to the selected configuration.

What is the difference between a WTI gauge and fiber optic hot spot monitoring?

A WTI gauge uses thermal simulation, while fiber optic hot spot monitoring directly measures temperature at selected winding measurement points. The two methods can serve different transformer monitoring requirements.

Где установлен датчик температуры?

The temperature bulb is installed in the compound transmitter, and the compound transmitter is inserted into the thermometer pocket on the top oil area of the transformer tank.

Request BWR2 Transformer Winding Temperature Indicator Configuration

For project selection, please provide the transformer type, required output signal, switch contact requirement, remote display requirement and installation environment. INNOFZ can help select a suitable BWR2 winding temperature indicator configuration for your transformer temperature monitoring application.